Open access
Date
2015Type
- Conference Paper
ETH Bibliography
yes
Altmetrics
Abstract
This paper investigates different control implementations for the frequency-response coupling between synchronous areas that feature a decentralized load-frequency control structure. The technical basics are presented, along with a 2-area benchmark system implemented in SIMULINK. Two new concepts are applied: Frequency-response delivery and frequency netting. The results show that both concepts are robust and stable. But as the frequency-response coupling affects the frequency performance in both the connecting and receiving synchronous area, the control scheme determines the overall system reliability. There are two reasonable options for the unilateral frequency-response delivery; the choice depends on the difference in the frequency restoration design between the synchronous areas. For frequency netting, only one scheme is applicable. Show more
Permanent link
https://doi.org/10.3929/ethz-b-000105093Publication status
publishedExternal links
Book title
2015 IEEE Eindhoven PowerTechPages / Article No.
Publisher
IEEEEvent
Subject
Frequency containment reserves; Frequency netting; Frequency-response; Primary frequency controlOrganisational unit
03559 - Andersson, Göran (emeritus)
More
Show all metadata