The use of air-conditioning, the largest energy demand for buildings in the tropics, is increasing as regional population and affluence grow. The majority of installed systems are split type air-conditioners. While the performance of new equipment is much better, the influence of the microclimate where the condensing units are installed is often overlooked. Several studies have used CFD simulations to analyse the stack effect, a buoyancy-driven airflow induced by heat rejected from condensing units. This leads to higher on-coil temperatures, deteriorating the performance of the air-conditioners. We present the first field measurements from a 24-storey building in Singapore. A network of wireless temperature sensors measured the temperature around the stack of condensing units. We found that the temperatures in the void space increased continuously along the height of the building by 10–13 °C, showing a significant stack effect from the rejected heat from condensing units. We also found that hot air gets stuck behind louvres, built as aesthetic barriers, which increases the temperature another 9 °C. Temperatures of around 50 °C at the inlet of the condensing units for floors 10 and above are the combined result, reducing the unit efficiency by 32% compared to the undisturbed design case. This significant effect is completely neglected in building design and performance evaluation, and only with an integrated design process can truly efficient solutions be realised.
Permanent link
Publication status
published
External links
Editor
Book title
Journal / series
Volume
71
Pages / Article No.
28 - 37
Publisher
Elsevier
Event
Edition / version
Methods
Software
Geographic location
Date collected
Date created
Subject
Air-conditioning; Tropical climate; Energy efficiency; Heat rejection; Split units; High-rise buildings; Temperature rise; Field measurements; Condensing unit
Organisational unit
03902 - Schlüter, Arno / Schlüter, Arno
03724 - Leibundgut, Hansjürg (emeritus)